PD-12IIB: combustible gas (e.g. hydrogen, isobutane, etc.)
PD-12IIC: hydrogen, helium, carbon dioxide, etc.
PD-12IIR: methane
PD-12IIB: catalytic combustion type
PD-12IIC: gas thermal conductivity type
PD-12IIR: non-dispersive infrared type
PD-12IIB: 0~100% LEL
PD-12IIC: 0~100 vol%
PD-12IIR: 0~100% LEL
Fault alarm: yellow LED flashes (sensor disconnection, sensor zero point drop, abnormal power supply voltage, etc.)
Toxic gas: ±30% of alarm set value under the same conditions
Toxic gas: alarm within 60 sec when concentration reaches 1.6 times the alarm set value
Gas alarm contact or fault contact *1: 1a voltage-free contact/auto reset
(Rated load: AC250V 0.5A or DC30V 0.5A (resistive load))
※Overseas explosion-proof standard ATEX certification obtained (specification must be designated at time of purchase)
PD-12IIR: low flow detection function (alarm when below 0.3L/min)
| During maintenance, output information can be checked directly from the detector unit. Calibration can be completed by one person, reducing maintenance costs
| Adjusted with a magnetic rod, making maintenance easy
| Waterproof and dustproof construction
| Protection rating IP65
| Flow rate drop detection function (optional)
| Explosion-proof specification for hydrogen gas