UV-810

Share:
Add to compare
Specification
Model
UV-810
UVB-810
External Output
Common alarm terminals
- 1st stage alarm contact voltage-free 1a (standard) (AC100V 1A, DC24V 1A resistive load)
- 2nd stage alarm contact voltage-free 1a (standard) (AC100V 1A, DC24V 1A resistive load)
- Buzzer contact voltage-free 1a (standard) (AC100V 1A, DC24V 1A resistive load)
- Fault contact voltage-free 1a (standard) (AC100V 1A, DC24V 1A resistive load)
※The 2nd stage alarm contact and 1st stage alarm contact can be changed to 1b contact (specification must be designated at time of purchase)
Individual alarm terminals
- 1st stage alarm contact voltage-free 1a (standard) (AC250V 2A, DC24V 2A resistive load)
- 2nd stage alarm contact voltage-free 1a (standard) (AC250V 2A, DC24V 2A resistive load)
Individual analog signal output terminals
- Gas concentration analog signal (4-20mA) (output drops to 0.9mA or below at fault alarm)
Load resistance of analog signal including wiring resistance must be 300Ω or below
Operating Temperature and Humidity Range
UV-810: -10~+40℃, 10~90% RH
(no drastic temperature or humidity change, non-condensing)
UVB-810: 0~+40℃, 10~90% RH
Power Supply
UV-810: AC100V~240V±10% [50/60Hz] ※When pump power supply is AC, power supply is AC100V
DC24V±10% (specification must be designated at time of purchase)
UVB-810: AC100V~240V±10% [50/60Hz]
Power Consumption
UV-810: - AC input (100V~240V) power consumption (VA) = (V3×n+VAS)×1.25 (SW power supply loss)
- DC input (24V±10%) power consumption (W) = V3×n+VAS
※n = number of connected V3 points; V3 includes the power consumption of the detector
UVB-810: Power consumption (VA) = (V3×number of connected points+VAS+18) × 1.25 (SW power supply loss)
※V3 includes detector power saving
Weight
UV-810: (3-point type) approx. 5.5kg~(15-point type) 13.5kg ※Including alarm and indicator
UVB-810: (3-point type) approx. 8kg (6-point type) 16kg ※Including alarm and indicator
Standard Accessories
UV-810: current fuse
UVB-810: current fuse x2
Product Features

 

|Panel-mounted type, freely combinable with V3 series indicators, alarms, and other gas detectors. One unit can detect multiple gases
|Standard wiring panel specifications are available in 3-, 6-, 9-, 12-, and 15-point types
|Only 103mm thick, with a clean, flat body design
|Choose the UVB-810 with backup power to keep the equipment operating normally even during a power outage (3- and 6-point types only)
| Single-point wiring boxes that can be installed in existing monitoring panels are available, along with standalone panels for multi-point monitoring
| Protection rating IP2X (when installed)

 

Privacy preferences

We use cookies to allow our website to function properly, personalize content and ads, provide social media features, and analyze traffic. We also share information about your use of our website with our social media, advertising, and analytics partners.

Privacy Policy

Manage Consent Preferences

Necessary Cookies

Always Active

These cookies are essential for the website to function, and you cannot turn them off in our systems. They are usually set only in response to actions you take that amount to a request for services, such as setting your privacy preferences, logging in, or filling out forms. You can set your browser to block or alert you about these cookies, but some parts of the website may then not work.

Inquiry Cart

total 0 items

Comparison Chart

Selected: 0