Alarm unit: VAS
Cv, Ci: catalytic combustion type
Tv, Ti: gas thermal conductivity type
D: potentiostatic electrolysis type
O: membrane galvanic cell type
M: according to detector specifications
Cv, Ci: combustible gas (LPG, methane, etc.)
Tv, Ti: hydrogen, helium, argon, carbon dioxide, methane
D: various semiconductor material gases, various toxic gases
O: oxygen
M: according to detector specifications
Combustible gas: within ±25% of alarm set value
Toxic gas: within ±30% of alarm set value
Oxygen: within ±1.0 vol% of alarm set value
[M] According to detector specifications
Combustible gas: alarm within 30 sec when concentration reaches 1.6 times the alarm set value
Toxic gas: alarm within 60 sec when concentration reaches 1.6 times the alarm set value
Oxygen: alarm within 5 sec when concentration reaches 10 vol% (oxygen deficiency)
[M] According to detector specifications
Stage 1: red ALARM1 alarm light flashes
Stage 2: red ALARM2 alarm light flashes
Alarm unit (VAS) alarm display: red ALARM alarm light lights up (off under normal conditions)
[Analog output] DC4~20mA
[VAS alarm contacts] 1c voltage-free for each of stage 1 and stage 2 (AC100V, 1A resistive load)
VAS operating temperature and humidity range: -10~+40℃, 10~90% RH
DC24V±10% (varies depending on the connected detector, may be 24V±6V)
[M] Approx. 5.0W (power consumption without connected suction type detector)
[VAS power supply] DC24V±10%
VAS power consumption: approx. 3.5W (when power supply is 24V and alarm is triggered)
VAS dimensions: W36×H144×D70mm (excluding protrusions)
VAS weight: approx. 600g including junction box (standard), approx. 520g (short)
| The indicator and alarm units can be combined with various gas detection devices to form a flexible detection and alarm system
| In addition to the alarm light and buzzer, the indicator's 3-color LED bar graph design makes it easier to confirm the alarm status
| Built-in maintenance mode stops external alarm output during maintenance. Maintenance can also be performed by a single person
| Can replace our existing alarm panels
| The indicator's buttons are protected by a cover to prevent operating errors
| Compliant with EU CE certification