AL2: 50% full scale or AL1, AL2: 25% full scale
2nd stage alarm: [ALARM] LED flashes red rapidly + LCD display (red) + buzzer sound (fast intermittent sound) + voice "Gas leak"
- Signal output: energized output DC0-6-12V
- 1st stage alarm contact output: 1a voltage-free AC250V 2A, DC30V 2A (resistive load)
- 2nd stage alarm contact output: 1a voltage-free AC250V 2A, DC30V 2A (resistive load)
- Buzzer contact: 1a voltage-free AC250V 2A, DC30V 2A (resistive load)
Individual
- Signal output: energized output DC0-6-12V
- 1st stage alarm contact output: 1a voltage-free AC250V 2A, DC30V 2A (resistive load)
- 2nd stage alarm contact output: 1a voltage-free AC250V 2A, DC30V 2A (resistive load)
- Pump power output: DC24V max. 0.3A
DC specification: DC24V±10%
DC specification: 2-point type 9.6~12.5W, 4-point type 17.9~23.3W, 8-point type 35.8~46.6W, 12-point type 53.8~70.1W
2-point type with backup power: W299mm x D71.5mm x H338mm
4-point type: W299mm x D71.5mm x H338mm
6-point, 8-point type: W496mm x D71.5mm x H338mm
10-point, 12-point type: W644mm x D71.5mm x H338mm
| Multi-point LPG detection alarm; one unit can connect up to 12 detectors ※Only gas detectors manufactured by our company can be connected
| Easy, effortless operation with a dial and a simple, clear menu interface
| Zero/sensitivity adjustment with one touch. Manual zero/sensitivity adjustment can be completed easily from the main unit alone, with no other tools or test instruments required
| Passed seismic tests for magnitude 7 earthquakes, and can continue monitoring for up to 2 days even during a power outage
| Alarms are announced by voice. Two languages can be combined, with support for Japanese, English, Chinese, and Korean